Buses, loads, shunts, and branches#
The passive network model includes bus types, composite loads, fixed shunts, and the branch pi equivalent.
Bus types#
The IDE field assigns each bus one of four roles. Type 1 buses carry fixed
injections. Type 2 buses host voltage-regulating machines; the regulation
contract is defined on the generator page. Type 3 buses are
swing buses: the voltage magnitude and angle are held, and the connected
machines absorb the system power balance. Type 4 buses are out of service:
they are excluded from the solve, together with everything connected to
them, and each exclusion is reported (ISOLATED_BUS).
Every electrical island must contain a swing bus; a case with a swingless
island is rejected, with the island's buses reported. A case may carry
several swing buses: each is held at its setpoint, and they jointly absorb
the balance. The entered VM and VA seed the iteration and do not
constrain the solution, except at swing buses, where VA sets the held
angle.
Loads#
A load consists of constant-power, constant-current, and constant-admittance components. With \(V\) the bus voltage magnitude in per unit, the consumed power is
Each coefficient is entered as the power consumed at \(V = 1.0\) per unit, in
MW and Mvar, and its sign is preserved as entered. Loads with STAT = 0 and
loads at out-of-service buses are excluded. In revision 34 cases,
distributed generation on a load (DGENP, DGENQ) is netted against the
consumption when DGENF is non-zero; DGENF = 0 leaves PL/QL unchanged
(v33 default). Only the constant-power terms are netted; ZIP coefficients are
passed through as entered.
An optional solve setting (low_voltage_load) tapers the constant-power
component below a chosen voltage to bound the current it draws at depressed
voltages. It is disabled by default, and the equations above then hold as
written.
Fixed shunts#
A fixed shunt is an admittance to ground. GL is the active power consumed
and BL the reactive power injected at \(V = 1.0\) per unit; both scale with
\(V^2\). Positive BL is capacitive (injection); negative BL is a reactor
(consumption).
Branches#
A branch is a pi equivalent: series impedance \(R + jX\) in per unit on the
system base, total line charging B split equally between the two ends, and
optional per-end admittances (GI, BI, GJ, BJ). Out-of-service
branches (STAT = 0) are excluded. Flows are reported at both terminals, so
the difference between the two ends is the branch loss. The branch rating
fields do not constrain the solution; they scale the loading percentages in
reports. The bus voltage limit fields (NVHI, NVLO, EVHI, EVLO) have
no effect on the solve.
Zero-impedance ties#
The network preparation can consolidate buses joined by negligible impedance. The case threshold controls which connections qualify. Consolidated buses share one reported voltage, and the result identifies each affected bus and connection. Use the case doctor to review these changes before a study.
System switching devices#
In-service system switching devices (revision 34 and later) solve as network branches. RAW and RAWX exports do not write these records. Review the export report before using an exported case.