Induction machines#
The steady-state induction-machine model includes the equivalent circuit, scheduled power, slip, load-torque laws, saturation, and locked-rotor behavior.
Equivalent circuit#
An induction machine is the standard double-cage equivalent circuit, per
unit on the machine base MBASE and rated voltage RATEKV. The terminal
voltage in machine per unit is the bus voltage
scaled by the ratio of the bus base voltage to the rated voltage. With \(v\)
the machine terminal voltage and \(s\) the slip,
and the machine draws \(P + jQ = v\,\bar{I}\) times MBASE from its bus, in
MW and Mvar, positive when operating as a motor.
Scheduled power#
PSET schedules the machine power in MW: a positive value draws power as a
motor, a negative value delivers power as a generator. PCODE selects the
scheduled quantity: 1 schedules the mechanical output power, 2 the
electrical power drawn.
Slip solution#
At the solved terminal voltage, the electromagnetic torque equals the load torque:
The result reports the slip, electrical power, reactive power, and stall state.
Load-torque laws#
TCODE selects the load-torque law. TCODE = 1 is the power law
\(\tau(\omega) = \omega^D\). TCODE = 2 is the polynomial form
with \(C_0\) chosen to normalize the curve at rated speed.
Saturation#
The equivalent circuit can include leakage and main-flux saturation. Leakage saturation changes stator reactance with current. Main-flux saturation changes the magnetizing reactance with internal voltage.
Stall (locked rotor)#
The locked-rotor state is the standard slip-one equivalent circuit. The result identifies a machine that operates in this state.