Distribution load models#
GPF supports all eight OpenDSS load models. Each model defines how active and reactive power change with terminal voltage.
Common terminal equation#
Let x = |V|/V_nom, where V is one load branch voltage and V_nom is its
nominal voltage. In the normal voltage region, each power channel is expressed
as a weighted sum of exponent responses:
GPF differentiates this equation analytically with respect to the real and imaginary voltage components.
OpenDSS model mapping#
The following table states the normal-region response.
Model |
Active-power response |
Reactive-power response |
Source meaning |
|---|---|---|---|
1 |
|
|
Constant power |
2 |
|
|
Constant impedance |
3 |
|
|
Motor load approximation |
4 |
|
|
Conservation voltage reduction |
5 |
|
|
Constant current magnitude |
6 |
|
|
Constant power with fixed-Q source policy |
7 |
|
|
Constant active power and fixed impedance Q |
8 |
Weighted ZIP |
Weighted ZIP |
ZIPV response with voltage cutoff |
For model 8, the first three ZIPV values weight the impedance, current, and
power terms for active power. The next three values provide the corresponding
reactive weights. The seventh value defines the cutoff voltage. GPF preserves
the entered weights and does not renormalize them.
Voltage-region policies#
Models 1, 3, 4, 5, and 8 use the normal response between VMinPU and VMaxPU.
Below VMinPU, current is interpolated toward the bounded low-voltage region.
Above VMaxPU, a matched impedance response preserves the boundary value while
preventing unbounded current behavior.
At or below VLowPU, a base-impedance response is used. This response keeps
current finite as voltage approaches zero. Model 2 remains its quadratic
response across all voltages and therefore needs no separate voltage policy.
Models 6 and 7 apply separate active and reactive boundary rules. Their active channel uses a boundary-matched impedance response, while their reactive channel uses the base-impedance response outside the normal region. This distinction preserves their OpenDSS semantics even where their normal-region equations match another model.
Model 8 multiplies both power channels by the smooth OpenDSS cutoff function:
The analytic derivative includes the derivative of this multiplier.
Connections and phases#
The entered total kW and kvar are divided across the active load
branches. A wye connection uses phase-to-neutral branch voltage. A delta
connection uses phase-to-phase branch voltage. Open-delta and missing-phase
loads retain only the branches that their conductor declarations create.
Power sign and operating-point updates#
Positive load power denotes consumption. Negative active or reactive values are accepted and retain the same voltage-response law, which permits source-like test cases without changing the current convention.
The snapshot parser retains daily profile references but does not execute an
OpenDSS time-mode simulation. A GPF operating-point schedule can apply explicit
active and reactive multipliers to the base operating point.
Validation#
The load equations are validated against OpenDSS terminal-current results. The test matrix covers all eight models, wye and delta connections, missing phases, positive and negative power, zero power, normal and limited voltage regions, and exact voltage boundaries. Network tests then verify the same laws inside complete feeder solutions.