Skip to main content
Ctrl+K

gpf

  • gpf User Guide
  • gpf Reference
  • gpf User Guide
  • gpf Reference

Section Navigation

User Guide

  • Getting started
  • Concepts
  • Transmission power flow
  • Distribution power flow
  • Mixed transmission-distribution power flow
  • Time-series power flow
  • Transmission contingency analysis
  • Tutorials
    • Working with Cases
    • Case management
    • Reports
    • Controls and Regulation
    • Scenario Study Workflow
    • Sensitivities
    • Transfer capability
    • Interconnection studies
    • PV curves and loading margin
    • QV curves and reactive margin
    • Optimal power flow
    • Transmission rights
  • Recipes
  • Use gpf from an AI agent
  • Modeling reference
    • Conventions
    • Phase-domain conventions
    • Distribution load models
    • Distribution device models
    • Buses, loads, shunts, and branches
    • Generators
    • Voltage droop control
    • Transformers
    • Switched shunts
    • HVDC: line-commutated links
    • HVDC: voltage-sourced converter lines
    • FACTS devices
    • Induction machines
    • Area interchange
  • gpf User Guide
  • Modeling reference
  • HVDC: line-commutated links

HVDC: line-commutated links#

The two-terminal line-commutated converter model enforces its scheduled quantities, converter angles, and tap limits.

Converter model#

Each terminal is a line-commutated converter of NBR (rectifier) or NBI (inverter) bridges fed through a converter transformer with ratio \(t\). With \(V_{ac}\) the per-unit AC terminal voltage, \(\theta\) the firing angle \(\alpha\) at the rectifier or the extinction angle \(\gamma\) at the inverter, \(X_c\) the commutating reactance, and \(I_d\) the direct current, the DC-side voltage of a converter follows the bridge relation

\[ V_d = \frac{3\sqrt{2}}{\pi}\, N_B\, t\, V_{ac} \cos\theta \;-\; \frac{3}{\pi}\, N_B\, X_c\, I_d , \]

and the two terminals are joined by the line resistance: \(V_{d,r} - V_{d,i} = R_{dc} I_d\).

Scheduled quantity#

MDC selects the scheduled quantity. Mode 1 holds the scheduled DC power SETVL in MW: a non-negative SETVL schedules the power at the rectifier, and a negative value schedules its magnitude at the inverter. Mode 2 holds the scheduled direct current SETVL in amperes. VSCHD is the scheduled DC voltage in kV, held by the voltage-controlling terminal. A nonzero compounding resistance RCOMP displaces the voltage-control point along the line by RCOMP times the direct current.

Angle and tap limits#

The rectifier holds the schedule with the firing angle inside [ANMNR, ANMXR]; the inverter holds the voltage with the extinction angle inside [ANMNI, ANMXI], all in degrees. The converter transformer taps move within [TMNR, TMXR] and [TMNI, TMXI] in steps of STPR and STPI to keep the angles inside their ranges. When an angle reaches a limit it is held there, and the operating point follows from the remaining relations.