Generators#
The generator model covers machine dispatch, voltage regulation, reactive limits, and wind-machine variants.
Dispatch and regulation#
An in-service machine at a type 2 bus injects its dispatched active power
PG and regulates a voltage to the setpoint VS. The regulated bus is the
machine terminal unless IREG names another bus (IREG = 0 selects the
terminal). Reactive output is a solution variable bounded by QB and QT.
Reactive limits#
At the solution, the controlled voltage equals the setpoint or the reactive output rests at a limit.
Swing machines#
Machines at type 3 buses hold the bus voltage: the magnitude at the machine
setpoint VS and the angle at the entered bus VA. The connected machines
absorb the active and reactive balance of the system.
Wind machines#
The WMOD field selects how reactive capability is derived. With
\(\tan\varphi = \sqrt{1 - \mathrm{WPF}^2}\,/\,|\mathrm{WPF}|\):
WMOD |
Behavior |
|---|---|
0 |
Conventional machine; |
1 |
Reactive limits taken from |
2 |
Voltage regulation with limits \(\pm\,\lvert PG\rvert \tan\varphi\). |
3 |
Fixed reactive output \(PG \tan\varphi\), signed by the sign of |